火电厂闭式循环水系统变工况运行优化

郑 姗, 张瑞山, 刘 明, 种道彤, 严俊杰

动力工程学报 ›› 2013, Vol. 33 ›› Issue (9) : 711-716.
辅机技术

火电厂闭式循环水系统变工况运行优化

  • 郑 姗1,2, 张瑞山3, 刘 明2, 种道彤2, 严俊杰2
作者信息 +

Off-design Operation Optimization for Closed Circulating Water System of Thermal Power Plants

  • ZHENG Shan1,2, ZHANG Ruishan3, LIU Ming2, CHONG Daotong2, YAN Junjie2
Author information +
History +

摘要

以某600 MW机组闭式循环水系统为例,提出了以汽轮机负荷、环境温度和环境相对湿度为条件的优化运行方式,将冷却塔、凝汽器和汽轮机变工况进行耦合,得到了闭式循环水系统冷却塔的进塔水温和出塔水温(即凝汽器循环水的出口温度和入口温度)随机组负荷、环境温度和环境相对湿度的变化规律.结果表明:在一定的环境条件和负荷下,进塔水温随循环水体积流量的增大而降低,而出塔水温随循环水体积流量的增大而升高;进塔水温和出塔水温均随着环境温度、环境相对湿度和机组负荷的升高而升高.

Abstract

Taking the closed circulating water system of a 600 MW power unit as an example, an optimized operation mode was proposed based on the load of steam turbine, the ambient temperature and the relative environment humidity, while a variation law obtained about how the inlet/outlet water temperature of cooling tower in the closed circulating water system (i.e. the outlet/inlet temperature of condenser) change with the unit load, ambient temperature and relative environment humidity by coupling variable conditions of the cooling tower, condenser and turbine.. Results show that with the rise of circulating water flow, the inlet temperature of cooling tower reduces, but the outlet temperature of cooling tower increases, under a certain environmental condition and load; both the inlet/outlet temperature of cooling tower increase with rising ambient temperature, relative environment humidity and unit load.

关键词

闭式循环水系统 / 变工况 / 循环水温度 / 优化运行

Key words

closed circulating water system / off-design condition / circulating water temperature / operation optimization

引用本文

导出引用
郑 姗, 张瑞山, 刘 明, 种道彤, 严俊杰. 火电厂闭式循环水系统变工况运行优化. 动力工程学报. 2013, 33(9): 711-716
ZHENG Shan, ZHANG Ruishan, LIU Ming, CHONG Daotong, YAN Junjie. Off-design Operation Optimization for Closed Circulating Water System of Thermal Power Plants. Journal of Chinese Society of Power Engineering. 2013, 33(9): 711-716

参考文献

[1] 田疆,刘继平,邢秦安,等.火电厂冷端在线监测诊断模型及其应用[J]. 热力发电,2004,33(3):14-16.
TIAN Jiang, LIU Jiping, XING Qinan, et al. Diagnosis model for on-line monitoring cooling end of thermal power plant and study on application thereof[J].Thermal Power Generation, 2004,33(3):14-16.
[2] 董丽娟,张润盘,张春发.循环水泵的优化调度[J].电力科学与工程,2007,23(1):73-78.
DONG Lijuan, ZHANG Runpan,ZHANG Chunfa.Optimization dispatching of water circulating pump[J].Electric Power Science and Engineering,2007,23(1):73-78.
[3] 王爱军,李艳华,张小桃,等.循环水泵优化运行方式的在线分析与研究[J].汽轮机技术,2005,47(2):130-132.
WANG Aijun,LI Yanhua,ZHANG Xiaotao,et al.Online analysis and research on optimum operation style of circulating water pump[J].Turbine Technology,2005,47(2):130-132.
[4] 何东辉. 火电厂冷端系统性能分析及优化研究[D].大连:大连理工大学, 2007.
[5] 马立恒,王运民. 火电厂凝汽式汽轮机冷端运行优化研究[J]. 汽轮机技术,2010, 52(2):137-140.
MA Liheng, WANG Yunmin. Study on the running optimization for condensing steam turbine cold end in thermal power plant[J].Turbine Technology,2010, 52(2):137-140.
[6] 王松岭,胡红丽,张学镭,等. 冷却塔出塔水温的数值模拟[J]. 动力工程,2005,25(增刊):455-459.
WANG Songling, HU Hongli, ZHANG Xuelei, et al. Numerical simulation of cooling tower outlet water temperature[J]. Chinese Journal of Power Engineering, 2005, 25(s):455-459.
[7] 李明. 冷端参数变化对冷却塔冷却性能的影响研究[J]. 东北电力大学学报,2010,30(1):5-9.
LI Ming. Study on the influence of cool-end parameters changing upon the cooling tower's performance[J]. Journal of Northeast Dianli University,2010,30(1):5-9.
[8] 赵振国,石金玲, 周常虹,等. 冷却塔的一个新的热力计算方法——用一维方法作二维计算[J].水利学报,2002(2):8-16.
ZHAO Zhenguo, SHI Jinling, ZHOU Changhong,et al. A new method for computation of counter-flow cooling tower[J]. Journal of Hydraulic Engineering, 2002(2):8-16.
[9] HAO Lijuan,LI Huanzhi,SUN Zhaohu,et al. Numerical simulation of air-cooling tower[J]. Journal of Thermal Science,2003,12(3):264-269.
[10] 徐跃芹,屠珊,黄文江,等,火电厂自然通风冷却塔性能研究[J].汽轮机技术,2005,47(5):357-359.
XU Yueqin,TU Shan,HUANG Wenjiang,et al.Research on performance of natural draft cooling tower in power plant[J]. Turbine Technology,2005,47(5):357-359.
[11] 李秀云, 林万超, 严俊杰. 冷端系统运行经济性诊断方法的理论研究[J]. 西安交通大学学报,2001,35(5):479-484.
LI Xiuyun, LIN Wanchao, YAN Junjie.Study on thermo-economics diagnosis method for cold-end system in steam power unit[J]. Journal of Xi'an Jiaotong University, 2001,35(5):479-484.
[12] 李秀云.火电机组冷端系统经济性诊断理论的研究[D].西安:西安交通大学,1999.
[13] 王冬. 自然通风冷却塔冷却性能计算模型及影响因素[D]. 保定:华北电力大学, 2007.
[14] 宋正昶,牛小川. 凝汽式电厂循环式供水冷端系统耦合数学模型[J].热力发电,2006,35(12):14-18.
SONG Zhengchang, NIU Xiaochuan.Coupling mathematical model of the cold end system for circulatory water supply in condensing power plant[J].Thermal Power Generation, 2006,35(12):14-18.
[15] 曾德良,王玮,杨婷婷,等. 基于换热理论的凝汽器压力应达值的确定[J].动力工程学报,2010,30(9):678-683.
ZENG Deliang, WANG Wei, YANG Tingting, et al. Determination of the target value of condenser pressure based on heat transfer theory[J]. Journal of Chinese Society of Power Engineering, 2010,30(9): 678-683.
[16] 王玮,曾德良,杨婷婷,等. 基于凝汽器压力估计算法的循环水泵最优运行[J]. 中国电机工程学报,2010,30(14):7-12.
WANG Wei, ZENG Deliang, YANG Tingting, et al. The optimum running of circulating water pumps based on estimated condenser pressure[J].Procee-dings of the CSEE, 2010,30(14):7-12.
[17] 史佑吉.冷却塔运行与试验[M].北京:水利电力出版社,1990:52-115.
[18] 赵振国. 冷却塔[M].北京:中国水利水电出版社,2001:24-30.
[19] 林万超. 火电厂热力系统节能理论[M].西安:西安交通大学出版社,1994:80-90.
[20] 严俊杰,黄锦涛,张凯,等. 发电厂热力系统及设备[M].西安:西安交通大学出版社,2006:301-303.

基金

国家重点基础研究发展规划资助项目(2009CB219803);国家自然科学基金资助项目(51125027,U126210);国家科技支撑计划资助项目(2011BAA04B03)

641

Accesses

0

Citation

Detail

段落导航
相关文章

/