Abstract:
With the continuous increase in the penetration rate of new energy power generation, and the primary frequency regulation performance of coal-fired units is crucial for maintaining grid frequency stability. It is essential to fully exploit the internal heat storage of units to further improve their primary frequency regulation capability. Taking a 330 MW coal-fired unit as the research object, the primary frequency regulation performance under different frequency regulation modes is compared. The results show that, under disturbance of 0.026 Hz, when the unit operating condition decreases from 75% turbine heat acceptance (THA) to 40%THA, the electricity contribution index drops from 80.1% to 75.0%, and the total additional exergy loss increases from 94.4 MJ to 119.1 MJ, indicating a significant degradation in frequency regulation performance. Under the 40%THA operating condition, the maximum bearable frequency disturbances corresponding to main steam valve regulation, main steam valve regulation assisted by high-pressure heater extraction throttling, main steam valve regulation assisted by condensate throttling, and multi-mode frequency regulation are 0.026 Hz, 0.036 Hz, 0.064 Hz and 0.081 Hz, respectively. Under the 0.030 Hz disturbance, the additional exergy loss per unit frequency regulation electricity of the main steam valve regulation assisted by high-pressure heater extraction throttling and that assisted by condensate throttling are 3275.1 MJ/MWh and 3656.6 MJ/MWh, respectively. The research results provide theoretical reference for the optimization of frequency regulation strategies for similar coal-fired units.