    限流构网型逆变器多类型故障暂态同步稳定性

    Transient Synchronization Stability of Current-Limited Grid-Forming Inverters under Multiple Fault Types

    • 摘要: 针对虚拟导纳型构网型逆变器,建立计及限流控制与功率耦合的暂态同步稳定分析模型,结合二阶准稳态关系与三状态变量数值求解,分析电压幅值跌落及正、负向相位跳变下的失稳机理,并通过仿真与实验验证。结果表明:在所研究工况下,幅值跌落时的稳定性受平衡点间距与功角动态共同影响,负向相位跳变时主要取决于平衡点间距,正向相位跳变后系统具有较强的自恢复能力;虚拟阻抗幅值不改变限流状态下不稳定平衡点的位置,虚拟阻抗与并网阻抗的阻感比对平衡点间距的影响相反。减小虚拟阻抗幅值及阻感比可改善暂态同步稳定性和电压支撑能力,功率耦合对稳定性的影响不可忽略。

       

      Abstract: A transient synchronization stability model incorporating current limiting and power coupling is established for virtual-admittance-based grid-forming inverters. Second-order quasi-steady-state relationships and numerical solutions of three state variables are combined to analyze instability mechanisms under voltage sags and positive and negative phase jumps. The analysis is validated through simulations and experiments. The results show that, under the investigated operating conditions, stability during voltage sags depends on both the separation between stable and unstable equilibrium points and power-angle dynamics, whereas stability under negative phase jumps is mainly governed by this separation. The system exhibits a strong self-recovery capability following positive phase jumps. The virtual impedance magnitude does not change the unstable equilibrium point under current limiting, while the resistance-to-reactance ratios of the virtual and grid impedances have opposite effects on the separation between equilibrium points. Reducing the virtual impedance magnitude and its resistance-to-reactance ratio improves transient synchronization stability and voltage support. The influence of power coupling on stability cannot be neglected.

       

    /