    基于AGC指令信号多模态分解的超超临界机组协调控制优化

    Coordinated Control Optimization for Ultra-Supercritical Units Based on Multi-Mode Decomposition of AGC Command Signals

    • 摘要: 针对AGC-R模式下负荷指令高频翻转引起的超超临界机组协调品质恶化问题,本文从指令信号多模态分解出发,建立尺度-通道映射准则,提出协调控制优化策略。分析AGC调度模式演变并提取指令统计特征后,采用变分模态分解识别指令的翻转尺度与趋势尺度结构,依据制粉-燃烧-传热过程的可响应性建立尺度-通道映射准则:趋势尺度进前馈、翻转尺度进衰减、残差进柔性死区。据此设计三个改进环节:R模式在线辨识配合S型轨迹规划柔化翻转指令,双惯性差分前馈提取趋势速率并衰减翻转激励,给水对燃料增量前馈配合四象限模糊增益抑制温度-压力耦合扰动。以某超超临界机组AGC-R工况真实DCS数据驱动的仿真结果表明:与常规协调控制相比,主汽压最大偏差降低18.4%、功率最大偏差降低12.0%,前馈高频振荡衰减83.5%;中间点温度最大偏差由11.60 ℃增至15.06 ℃,为以温度控制精度小幅代价换取压力与功率品质提升的权衡,其值仍低于机组现场实测水平,验证了策略的有效性与工程应用价值。

       

      Abstract: To address the deterioration of coordinated control quality of ultra-supercritical units caused by high-frequency flipping load commands in AGC-R mode, this paper proposes a coordinated control optimization strategy based on multi-mode decomposition of command signals, in which a scale-to-channel mapping criterion is established. After analyzing the evolution of AGC dispatching modes and extracting the statistical characteristics of the commands, the variational mode decomposition is employed to identify their flipping-scale and trend-scale structures, based on which the scale-to-channel mapping criterion is established according to the responsiveness of the milling-combustion-heat transfer process: the trend scale feeds the feedforward baseline, the flipping scale is attenuated, and the residual scale enters a flexible dead zone. Accordingly, three improvement blocks are designed: online identification of R mode with S-curve trajectory planning to soften the flipping commands, a double-inertia differential feedforward to extract the trend rate and attenuate flipping excitation, and a water-to-fuel incremental feedforward with four-quadrant fuzzy gain to suppress temperature-pressure coupling disturbance. Simulation results driven by real DCS data of an ultra-supercritical unit under AGC-R conditions show that, compared with conventional coordinated control, the maximum deviation of main steam pressure is reduced by 18.4%, the maximum deviation of power by 12.0%, and the high-frequency feedforward oscillation is attenuated by 83.5%, while the maximum deviation of the intermediate point temperature increases from 11.60 °C to 15.06 °C as a trade-off for the pressure and power improvement and remains below the field measured level, which verifies the effectiveness and engineering applicability of the proposed strategy.

       

    /

    返回文章
    返回