高级检索

    考虑火电运行平稳性的飞轮储能辅助二次调频控制策略

    Secondary Frequency Control Strategy Assisted by Flywheel Energy Storage Considering Operation Stability of Thermal Power Plant

    • 摘要: 为解决电网波动剧烈导致的火电机组运行平稳性问题,提出一种考虑火电运行平稳性的飞轮储能辅助二次调频控制策略。首先,建立了超超临界火电机组联合飞轮储能的二次调频控制模型;其次,提出了一种基于多层变增益速率限制的AGC指令非线性分解方法;最后,综合机组平稳性和系统AGC性能设计了适应度函数,借助鲸鱼优化算法(WOA)实现了最优化的速率限制算法参数获取。基于上述方法设计了火储协同二次调频控制策略。以某1 000 MW火电机组-飞轮储能联合系统为例进行了仿真验证。结果表明:所提控制策略在不影响系统调频性能的前提下可以使联合系统有效响应系统高频指令,减小了火电机组的动作幅度,提升了机组运行的平稳性。

       

      Abstract: To solve the issue of un-stable operation of thermal power units caused by severe fluctuations in the power grid, a secondary frequency regulation control strategy assisted by flywheel energy storage considering the operation stability of thermal power plant was proposed. Firstly, a secondary frequency regulation control model for ultra-supercritical thermal power units integrated with the flywheel energy storage was developed. Then, a non-linear decomposition method for AGC instructions based on constraints of multi-layer variable gain rates was proposed. Finally, a fitness function was designed based on the unit stability and the AGC performance of the system, and the whale optimization algorithm (WOA) was used to obtain the optimal parameters of limiting algorithm. Based on the above method, a collaborative control strategy of secondary frequency regulation was designed for the integrated system of thermal power unit and energy storage. A simulation verification was conducted on the integrated system with a 1 000 MW thermal power unit and flywheel energy storage as an example. The results show that the proposed control strategy can effectively respond to high-frequency commands of the integrated system without affecting the frequency regulation performance, reduce the action amplitude of thermal power unit, and improve the stability of power unit operation.

       

    /

    返回文章
    返回